SICAM PAS connection to Micom P543 IEC-61850 Case Failed to Connect

SICAM PAS connection to Micom P543 IEC-61850 Case
SICAM PAS connection to Micom P543

SICAM PAS connection to Micom P543 IEC-61850 Case Failed to Connect

SICAM PAS connection to Micom P543 IEC-61850 Case Failed to Connect

I have written the case of Micom P543 Failed to Connect to SICAM PAS. Now, this is the update after some trial integration.


Here is some process that I have tried to connect Micom P543 to SICAM PAS:
  1. Upgrade the SICAM PAS V8.10 to V8.13 (Failed)
  2. Upgrade the Windows 7 Pro to Windows 10 Pro in Advance PC Server (Failed)
  3. Using USB converter to LAN (Failed)
  4. Erase Teaming Network (Failed)
  5. Change the redundancy setting in SICAM PAS (Failed)
The good news is when I use my Laptop to Communicate with Micom P543, the connection is running normally. 

The last step that I tried is installing the SICAM IEC Browser to the PC Server, then I realized that the connection like blocked by something. See the picture:

SICAM PAS connection to Micom P543 IEC-61850 Case Failed to Connect

While I am using the HMI PC the IEC Browser running Normal, see the picture:

SICAM PAS connection to Micom P543 IEC-61850 Case Failed to Connect

I might need to try installing the SICAM PAS into the HMI PC, and it should be running Normally. I mean the SICAM PAS Connection to Micom P543. But, the question is, what makes the PC Server Block the Connection to Micom P543?